Trade Guide

What Size Wire for a 100 Amp Subpanel?

The counter answer is #3 copper or #1 aluminum. The useful answer is why — which temperature column you are allowed to use, what derates it, and what the other three conductors have to be.

The short answer

#3 Copper or #1 Aluminum — Under the Usual Conditions

Both land on 100 amps in the 75°C column of NEC Table 310.16. The conditions decide whether that column applies to your feeder.

Table 310.16 is the ampacity table for insulated conductors run in a raceway, cable, or earth, with not more than three current-carrying conductors, at a 30°C (86°F) ambient. Every figure in it is a starting point, not a finished answer.

The table has three temperature columns: 60°C, 75°C, and 90°C. Which one you may size from is not decided by the wire. It is decided by the terminations at both ends, under NEC 110.14(C). Unless the equipment at both ends is listed and marked for something higher, the 75°C column is what you get on a feeder of this size. THHN is 90°C insulation, but 90°C wire landed on a 75°C lug is still a 75°C circuit.

The 90°C rating still matters: you may begin derating calculations from the 90°C ampacity, as long as the final corrected value does not exceed the termination rating.

Table 310.16, 75°C column

Where 100 Amps Falls

Sizes electricians actually consider for a 100-amp feeder. Confirm against the table in the edition adopted for your job.

Conductor sizeCopper, 75°CAluminum / copper-clad aluminum, 75°C
4 AWG85 A65 A
3 AWG100 A75 A
2 AWG115 A90 A
1 AWG130 A100 A
1/0 AWG150 A120 A

That is why the counter answer is #3 copper or #1 aluminum: they are the smallest sizes in each metal that reach 100 amps at 75°C. Many installers pull #2 copper or 1/0 aluminum anyway, for headroom on derating and voltage drop. Copper building wire is normally THHN/THWN-2; aluminum feeder wire is usually XHHW-2.

Read this before you cut

Six Things That Move the Answer

Method

How to Size It Without Guessing

Establish the load, then the breaker

Calculate the feeder load per Article 220, adding 125% for continuous loads. The breaker size follows the calculation, not the other way around.

Confirm the termination markings

Check the labels in both panels. That marking, per 110.14(C), sets the column you may use in Table 310.16.

Apply adjustment and correction

Count current-carrying conductors and identify the worst ambient the run passes through, then apply the factors in NEC 310.15. That numbering shifted in recent cycles, so navigate by title.

Check voltage drop on long runs

Long runs deserve the calculation. If you upsize the ungrounded conductors for voltage drop, NEC 250.122(B) requires the equipment grounding conductor to be increased proportionally.

Size the raceway last

Conduit fill comes from Chapter 9, Table 1 and Annex C. Fill is where a correct feeder becomes a pull you cannot make.

The other three conductors

Neutral, Ground, and the Four-Wire Feeder

A subpanel gets a four-wire feeder: two ungrounded conductors, a grounded (neutral) conductor, and an equipment grounding conductor. The neutral is sized for the maximum unbalanced load per NEC 220.61, but it cannot drop below the minimum size required for bonding purposes in NEC 250.102(C) and its table — look both up, because a reduced neutral that ignores the second rule is a common correction.

Size the equipment grounding conductor from NEC Table 250.122, using the rating of the overcurrent device ahead of the feeder. Read the row in your adopted edition rather than working from a number someone told you.

Keep neutrals and grounds separated at the subpanel. The neutral bar must be isolated from the enclosure — the main bonding jumper or bonding screw stays out — and the equipment grounding conductors land on a separate ground bar bonded to the can. The system is bonded once, at the service, and this is the most common thing an inspector red-tags on a subpanel. The old allowance for a three-wire feeder to a separate structure was removed for new installations in the 2008 NEC; on an existing three-wire feed, that is a conversation with your AHJ.

We stock what this takes — see our wire, cable, and conduit inventory for THHN/THWN-2, aluminum feeder wire, EMT and PVC, and our load centers, panelboards, and breakers for the subpanel, feeder breaker, and ground bar. We cut wire to length at the counter — send us the run length and breaker size for a same-day quote.

Reference only. This page is general reference information, not a substitute for the currently adopted code or the ruling of the authority having jurisdiction. California adopts the NEC as the California Electrical Code (Title 24, Part 3) with state amendments, and your city or county may amend it further. Requirements change from one code cycle to the next — verify every value against the edition in force for your permit, and confirm the details with your inspector before you buy material or energize anything. Ora Electric Lighting & Supply is a wholesale distributor. We sell materials. We do not perform electrical work, and we do not provide design or engineering services.

Common questions

Frequently Asked Questions

Is #3 copper always right for a 100 amp subpanel?
No. #3 copper reaches 100 amps in the 75°C column of NEC Table 310.16, which is the column most terminations allow under 110.14(C). If you have more than three current-carrying conductors in the raceway, a high ambient temperature, a wiring method limited to the 60°C column such as NM-B, or a long run with voltage drop, the required size goes up. Run the conditions for your install.
Can I use aluminum for a 100 amp subpanel feeder?
Yes, where the terminations are listed for aluminum. #1 aluminum reaches 100 amps at 75°C in Table 310.16. Aluminum feeder wire is typically XHHW-2 rather than THHN, it has a larger diameter at the same ampacity so recheck conduit fill, and it requires an antioxidant compound where the manufacturer's instructions call for one.
Does a 100 amp subpanel need a four-wire feeder?
For current work, yes: two ungrounded conductors, a grounded (neutral) conductor, and an equipment grounding conductor. Neutrals and grounds are kept separated at the subpanel — the neutral bar is isolated from the enclosure and the bonding screw stays out. The old three-wire allowance to a separate structure was removed for new installations in the 2008 NEC.
What size ground wire goes with a 100 amp feeder?
Size the equipment grounding conductor from NEC Table 250.122 using the rating of the overcurrent device ahead of the feeder, and read the row in the edition adopted for your job. If you upsize the ungrounded conductors for voltage drop, 250.122(B) requires the EGC to be increased proportionally.
Do you cut feeder wire to length?
Yes. We cut wire to length at the counter in Van Nuys. Give us the run, the size, and the colors you need and we will cut it and quote it the same day.
Related categories

Explore More of Our Inventory

Pricing a subpanel feeder?

Send us the run length and breaker size. Same-day quote, wire cut to length.

Request a Quote
📞 Call Us Now